Interpretation #6966

Published April 26, 2012

Original Request

Code Version
2010
Code
RESIDENT
Code Description
Residential
Chapter
3
Section
R310.1
Topic
wrap around porch

Question

Is it the intent of this section to not allow a porch completely around a house as this would not meet the open to the atmosphere.

Answer Published 04/26/2012 at 9:57 AM

No. The exception allows emergency escape and rescue
openings to open into a screened porch as long as the
screen porch is open to the atmosphere an leads directly to
yard, court, or public way. The screen enclosure must be
provided with a door leading away from the residence.

Commentary

Should the porch not be screened a person exiting the emergency escape could proceed directly away from the residence. Unless the porch is elevated, then there is the guardrail and drop which must be negotiated. Should the porch be screened it would be necessary to have a door through the screen enclosure in close proximity to the emergency escape. Otherwise one must move around the porch to find a door in the screened in porch instead of immediately moving away from a dangerous situation, perhaps creating panic and complicating the escape. A case-by-case review by the building official may be appropriate in order to ensure the level of intended life safety is not compromised.