Interpretation #6964

Published April 26, 2012

Original Request

Code Version
2010
Code
RESIDENT
Code Description
Residential
Chapter
11
Section
403.6.1.1
Topic
documentation

Question

Is it the intent of the Code to have dealers/contractors submit documentation of manufacturer's expanded ratings (total and sensible capacities along with design CFM)along with their permit application?

Answer Published 04/26/2012 at 9:55 AM

Yes. FBC-EC Section 103.2.2 requires the construction
documents to include "mechanical system design criteria;
mechanical and service water heating system and equipment
types, sizes and efficiencies..."

Commentary

Applicants must submit whatever the Building Official deems necessary to confirm Code Compliance, per FBC 107.3.