Interpretation #6956

Published April 04, 2012

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
1
Section
Energy Table 502.1.1.1(1)
Topic
2010 Energy Conservation Code

Question

Is it the intent of the 2010 FLA Building, Energy Conservation Code, Table 502.1.1.1(1) to provide minimum thickness on roof insulation at any one point on the roof, (under drains) to meet R-40 if an average R-40 value thickness over the entire roof can be met reducing the roof insulation at drain locations to less than R-40?

Answer Published 04/04/2012 at 3:10 PM

Yes. 502 is a prescriptive compliance path. As such the
thermal envelope minimums are more restrictive in order
to achieve the 80% passing score.

Commentary

The prescriptive path is required for shell buildings and renovations. However, any building may comply with method 506. If a shell building is to comply with method 506, then all assumed items must be listed and appended to the calculation. If the final build-out is not per the appended document, then a revised form 506 must be submitted at the time of final build-out of the building or portion of the building.For buildings complying with form 506, the performance method allows for trade offs and the average value of insulation could be used in the calculating of the compliance. Form 502 would not allow using a weighted average.