Interpretation #6954

Published March 20, 2012

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
1
Section
102.8
Topic
roof top support for mechanical equipment

Question

Is it the intent of section 102.8 of the 2010 Florida Building Code to require an equal change out of a roof top mechanical unit to comply with section 1509.7?

Answer Published 03/20/2012 at 10:41 AM

Yes. When the A/C unit is replaced, the clearances
in Table 1509.7 are required. Minimum clearances
for roof curbs is also required for those installations.

Commentary

None.