Interpretation #6944

Published March 08, 2012

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
1
Section
105.15
Topic
opening protection

Question

Is it the intent of code section 105.15 to require all existing openings including garage doors/skylights/exterior doors/windows on single family structures to have opening protection added when located within the wind borne debris region, the home was not constructed under the Florida Building Code, the proposed work is at least $50,000.00 and the insured value/ad valorem taxation is $750,000.00 or more?

Answer Published 03/08/2012 at 10:43 AM

Yes, all glazed openings must be protected.

Commentary

If the residence had been constructed under the Florida Building Code it would be exempt from the requirement to install impact protection.