Interpretation #6938

Published March 08, 2012

Original Request

Code Version
2007
Code
BUILDING
Code Description
Building
Chapter
15
Section
1507.1
Topic
cantilevered concrete canopy

Question

Is it the intent of FBC-B Section 1502 � Definitions, to describe a cantilevered concrete canopy or concrete roofed plaza covering the buildings entrances as a roof deck that would require roofing or a waterproofing system? If so, per FBC-B Section 1507.1 and 1507.15 the roof deck shall have a roof covering system or liquid-applied coating, or would standard paint be sufficient protection?

Answer Published 03/08/2012 at 10:45 AM

Yes, based upon the description of the canopies they would
meet the definition of roof deck, which then triggers
installation of an approved roof covering. However, the
definition of roof deck is so broad that there seems
to be room for interpretation depending on the nature of
the cantilevered concrete structures above the building
entrances, the manner of their construction and the amount
of concrete cover over reinforcing steel. The Building
Official should make the decision based upon specific
conditions.

Commentary

None.