Interpretation #6925

Published June 01, 2012

Original Request

Code Version
2007
Code
BUILDING
Code Description
Building
Chapter
10
Section
1006.2.3.2
Topic
circuit breakers

Question

Is it the intent of section 1006.2.3.2, specifically the statement "...opening of a circuit breaker or fuse or any manual act(s)..." to be applied to all circuit breakers or fuses that serve emergency lighting circuits or is the intent that this statement only applies to those circuit breakers or fuses that serve normal (non- emergency) lighting circuits.

Answer Published 06/01/2012 at 11:06 AM

It is not the intent of these sections to require battery
backup on everything. The last word of section 1006.2.3.2
is "facilities". This means the lighting system, not the
individual branch circuits.