Is it the intent of FPC Table 403.1 to require a
service sink for a tenant space intended to be
used as a small bar or tavern which has been
designated by the building code as Group M
Occupancy due to its occupancy load (less than
50 persons per FBC 303.1.1).
Interpretation #6917
Published March 08, 2012
Original Request
- Code Version
- 2007
- Code
- PLUMBING
- Code Description
- Chapter
- 4
- Section
- 403.1
- Topic
Question
Answer Published 03/08/2012 at 10:50 AM
FBC-P 403.1 says that the occupancy classification shall be
determined in accordanve with the FBC Building. FBC-
Building section 303.1.1 classifies it as Mercantile.
Therefore, you apply Table 403.1 using Mercantile
occupancy, which does not require a service sink.
determined in accordanve with the FBC Building. FBC-
Building section 303.1.1 classifies it as Mercantile.
Therefore, you apply Table 403.1 using Mercantile
occupancy, which does not require a service sink.