Interpretation #6916

Published March 08, 2012

Original Request

Code Version
2007
Code
BUILDING
Code Description
Chapter
9
Section
911.1.5
Topic

Question

Is it the intent of Section 911.1.5 to provide
individual control of all building air handling
systems from the fire command center in all
modes of operation, i.e. should the controls be
capable of over-riding the fire alarm functions
of the building (shutdown)?

Answer Published 03/08/2012 at 10:51 AM

Yes. This section is separate and distinct from section 6
which addresses smoke control system panels.

Commentary

Note: This language is also contained in the FFPC NFPA 1 section 11.9.5. The design professional should consult with the local Building Official and Fire Official regarding the need for override control of each separate HVAC system. The local Fire and Building Official, in consultation with the design professional, may determine that the need for this level of control for all air handling systems is not appropriate based on the hazard and system design.