Interpretation #6915

Published March 08, 2012

Download Final PDF

Original Request

Code Version
2007
Code
BUILDING
Code Description
Building
Chapter
9
Section
911.1.14
Topic

Question

Is it the intent of Section 911.1.14 to require from the fire command center the ability to manually transfer from normal to emergency power, or vice-versa, all automatic transfer switches connected to the emergency electrical system of the building? Is the requirements of line item 14 intended to be different from that of line item 9?

Answer Published 03/08/2012 at 10:52 AM

Yes, the provision is intended to provide transfer switch
control in the Fire Command Center. Yes, the requirement in
line 14 is from line 9. Item 9 states "power status
indicators." Item 14 is supervision, start and transfer
features.

Commentary

This identical wording is contained in the FFPC NFPA 1 section 11.9.5 (7) and (9). Considering this is an existing building, the Building Official and Fire Official should be consulted to determine the need and feasibility for compliance with the specific provision of this section and the FFPC based on the scope of the work and the work area.