Interpretation #6914
Published March 09, 2012
Original Request
- Code Version
- 2007
- Code
- BUILDING
- Code Description
- Building
- Chapter
- 7
- Section
- 716.6.1
- Topic
Question
Is it the intent of Section 716.6.1 "Through Penetrations" to be applied ONLY to thru penetrations in fire-resistance- rated floor/ceiling assemblies, or is it to be applied to all through penetrations in any fire-rated assembly?
Answer Published 03/09/2012 at 3:59 PM
A shaft is required. Section 716.6 says "shall be protected
by a shaft enclosure ..." and then says "or shall comply
with Sections 716.6.2.1 through 716.6.3. However the
exception in 716.6.1 is not allowed for a Group I-2
Occupancy.
by a shaft enclosure ..." and then says "or shall comply
with Sections 716.6.2.1 through 716.6.3. However the
exception in 716.6.1 is not allowed for a Group I-2
Occupancy.
Commentary
None.