Interpretation #6912

Published January 20, 2012

Download Final PDF

Original Request

Code Version
2007
Code
BUILDING
Code Description
Building
Chapter
10
Section
1024.1
Topic
Egress through lobby

Question

Is it the intent of 1024.1 exception 1 to allow an exit enclosure from a rated stairwell to egress though a lobby and then through a separate enclosed vestibule to the exit discharge.

Answer Published 01/20/2012 at 10:33 AM

Yes. See Interpreation #6895.

Commentary

However, If the building is a high-rise building, with some exceptions, 1020.1.7.1 would not allow the proposed configuration. As a practical matter in a high- rise building all exits must discharge to the outdoors, so as to access a public way.