Interpretation #6912
Published January 20, 2012
Original Request
- Code Version
- 2007
- Code
- BUILDING
- Code Description
- Building
- Chapter
- 10
- Section
- 1024.1
- Topic
- Egress through lobby
Question
Is it the intent of 1024.1 exception 1 to allow an exit enclosure from a rated stairwell to egress though a lobby and then through a separate enclosed vestibule to the exit discharge.
Answer Published 01/20/2012 at 10:33 AM
Yes. See Interpreation #6895.
Commentary
However, If the building is a high-rise building,
with some exceptions, 1020.1.7.1 would not allow the
proposed configuration. As a practical matter in a high-
rise building all exits must discharge to the outdoors, so
as to access a public way.