Interpretation #6901

Published January 25, 2012

Original Request

Code Version
2007
Code
EXTBLDG
Code Description
Existing Building
Chapter
5
Section
506.2
Topic
Repairs - substantial damage

Question

Is it the intent of the code here to allow for repairs/rebuilding of buildings which have suffered substantial damage from fire or other peril to be repaired/rebuilt subject only to the requirements of Chapter 5, or are substantial repairs (replacement of walls, finishes, ceilings, framing etc) to be considered Level 1 alteration?

Answer Published 01/25/2012 at 2:25 PM

No. Repairs are accomplished in accordance with Chapter 5
for work on non-damaged components that is necessary for
the repair and maintenance of a structure are considered
part of the repair and are not subject to Chapters 6, 7, 8,
9, and 10.

Commentary

The questions appears to describe a renovation of a building. WEBSTER: "RENOVATE: to restore to a former better state such as repairing or rebuilding". Renovation is part of the definition of ALTERATION. As to the level of alteration; in accordance with FBCE 401.4 The alteration level is chosen by the design professional or the owner.