Interpretation #6877

Published December 23, 2011

Original Request

Code Version
2007
Code
EXTBLDG
Code Description
Existing Building
Chapter
9
Section
912.2.1
Topic
Fire Sprinkler : A-2 Occupancy

Question

Is it the intent of the Florida Building Code, Existing Building, section 912.2.1 to require the installation of a fire sprinkler system in an existing un-sprinkled (A-2) restaurant with an existing occupant count of over 100 persons when adding an outside seating/dinning area increasing the restaurants occupant count further beyond limits of section 903.2.1.2 of the Building Code.

Answer Published 12/23/2011 at 6:02 PM

Section 912.2.1 refers to a "change in occupancy". In the case described there is
no change of occupancy occurring. However, the simple answer is YES in
accordance to section 903.2.1.2 of the Building Code as mentioned in the
question.

Commentary

Check with the local Building Official as he/she may consider: 1. The occupant load of the building may not increase and; 2. The outside seating area is true open air and; 3. The outside seating area has an independent means of egress that does not require access through the building and that FBC section 903.2.1.2 refers to "fire areas" which if properly separated (2-hr) may do away with the requirement for Fire Sprinklers.