Interpretation #6877
Published December 23, 2011
Original Request
- Code Version
- 2007
- Code
- EXTBLDG
- Code Description
- Existing Building
- Chapter
- 9
- Section
- 912.2.1
- Topic
- Fire Sprinkler : A-2 Occupancy
Question
Is it the intent of the Florida Building Code, Existing Building, section 912.2.1 to require the installation of a fire sprinkler system in an existing un-sprinkled (A-2) restaurant with an existing occupant count of over 100 persons when adding an outside seating/dinning area increasing the restaurants occupant count further beyond limits of section 903.2.1.2 of the Building Code.
Answer Published 12/23/2011 at 6:02 PM
Section 912.2.1 refers to a "change in occupancy". In the case described there is
no change of occupancy occurring. However, the simple answer is YES in
accordance to section 903.2.1.2 of the Building Code as mentioned in the
question.
no change of occupancy occurring. However, the simple answer is YES in
accordance to section 903.2.1.2 of the Building Code as mentioned in the
question.
Commentary
Check with the local Building Official as he/she may consider:
1. The occupant load of the building may not increase and;
2. The outside seating area is true open air and;
3. The outside seating area has an independent means of egress that does not
require access through the building and that FBC section 903.2.1.2 refers to
"fire areas" which if properly separated (2-hr) may do away with the
requirement for Fire Sprinklers.