Interpretation #6862

Published November 08, 2011

Original Request

Code Version
2007
Code
PLUMBING
Code Description
Plumbing
Chapter
3
Section
312.1
Topic
Plumbing system testing

Question

Is it the intent of the required tests, to test all plumbing system piping with water or if other than plastic with air, or to prevent PVC or Foam Core PVC being tested with air?

Answer Published 11/08/2011 at 12:02 AM

All plumbing system piping shall be tested with either
water or by air. Except that Plastic piping is to be tested
by water unless tested as specified in Section 312.3.

Commentary

The intent is to prevent excessive pressure being utilized on a plastic system in order to prevent a rupture and possible injury to personnel. Section 312.3 allows a 5 psi air test to be performed on DWV (plastic) systems. These tests are quick, easy and involve no risk of freeze damage.