Interpretation #6857

Published October 26, 2011

Original Request

Code Version
2007
Code
PLUMBING
Code Description
Plumbing
Chapter
4
Section
410
Topic
Bottled Water Dispenser Exception

Question

Is it the intent of Section 410.1 to allow a bottle water dispenser in a mercantile space of 751 square feet instead of a drinking fountain.

Answer Published 10/26/2011 at 11:09 AM

No. The bottled water coolers are allowed to replace only
50% of the required drinking fountains. As a practical
matter, this usually means that one wheelchair accessible
drinking fountain must be provided. A second drinking
fountain must be provided to accommodate patrons that
cannot bend over to access the wheelchair accessible
drinking fountain. The bottled water cooler with cup
dispenser may be provided in lieu of this second drinking
fountain.

Commentary

None.