Interpretation #6855

Published October 26, 2011

Original Request

Code Version
2007
Code
EXTBLDG
Code Description
Existing Building
Chapter
13
Section
1301.1
Topic
Tenant separation wall

Question

Is it the intent of the code to cover adding a second tenant, both tenants of type "B" occupancy to a building that was previously occupied by a single "B" tenant, so that a tenant seperation wall may not necessarily be required, at the discretion of the code official

Answer Published 10/26/2011 at 2:19 PM

No. FBC Building 708.1, 7 would apply. None of the
associated exception would apply. The wall needs to be
rated.

Commentary

By creating an additional tenant space, a tenant separation fire partition is required. see FBC 708.1, #7. The local Building Official may determine if some exemptions apply; such as if the space is a business less than 3,000 sq feet total and the original tenant sublets' the 3,000 sq feet into smaller business areas OR if a designer chooses to utilized chaper 13, the compliance alternatives scoring system MAY result in an arrangement that MAY not require tenant separation. Again, the Building Official can make a determination based on a code analysis of the entire situation.