Interpretation #6847

Published October 25, 2011

Original Request

Code Version
2007
Code
BUILDING
Code Description
Building
Chapter
6
Section
602.1
Topic
Canopy Structure

Question

Is it the intent of sections 602.1, 704.8 and of table 602 to consider the spaces between columns in a free-standing, canopy type structure as an opening in a wall even if there is no "wall" as such?

Answer Published 10/25/2011 at 10:47 AM

If it falls within the definition of "CANOPY" then
technically it has no walls. Hoewever, in accordance with
602.1 "the building elements shall have a fire-resistance
rating not less than that specified in Table 601" and Table-
602 would also apply (subnote B may apply if it's a "U"
occupancy). If the occupancy type is a "U", see 406.1.2 #2.

Commentary

The local Building Official will make the determination regarding the occupancy type and T-601 and T-602 applicability. Additional details for canopies are addressed in section 3105.