Interpretation #6844

Published October 19, 2011

Original Request

Code Version
2001
Code
BUILDING
Code Description
Building Codes
Chapter
1
Section
1403.1.4
Topic
1

Question

Is it the intent of 1403.1.4 to permit a private provider on a project to approve the use of caulking in lieu of flashing as required by FBCB 2001, Section 1403.1.4 in a fully and easily accessible location without the approval of the building official?

Answer Published 10/19/2011 at 8:25 AM

No, 1403.1.4 states "Caulking shall be provided where such
flashing is determined by the BUILDING OFFICIAL to
be impractical". It is the BO's right and responsibility to
determine if standard flashing is impractical, not a
private provider.

Commentary

The only person authorized by Florida Building Code section 104.11 and by Florida Statute to allow "alternate methods" to the code is the Building Official.