Interpretation #6836

Published September 28, 2011

Download Final PDF

Original Request

Code Version
2007
Code
EXTBLDG
Code Description
Existing Building
Chapter
7
Section
704.2.1
Topic
sprinklers

Question

Is it the intent of section 704.2.1 Existing Building Code to require a non sprinkled high rise condominium structure to become fully sprinkled because of a Level 2 alteration in one condo unit?

Answer Published 09/28/2011 at 4:06 PM

No. The scope of 704.1 indicates that it is limited to the
work area in which the level 2 alteration is being
performed.

Commentary

It should be noted that fire codes may require the building to be sprinklered throughout regardless of whether any work is done.