Interpretation #6836
Published September 28, 2011
Original Request
- Code Version
- 2007
- Code
- EXTBLDG
- Code Description
- Existing Building
- Chapter
- 7
- Section
- 704.2.1
- Topic
- sprinklers
Question
Is it the intent of section 704.2.1 Existing Building Code to require a non sprinkled high rise condominium structure to become fully sprinkled because of a Level 2 alteration in one condo unit?
Answer Published 09/28/2011 at 4:06 PM
No. The scope of 704.1 indicates that it is limited to the
work area in which the level 2 alteration is being
performed.
work area in which the level 2 alteration is being
performed.
Commentary
It should be noted that fire codes may require the
building to be sprinklered throughout regardless of whether
any work is done.