Interpretation #6824

Published September 14, 2011

Original Request

Code Version
2007
Code
EXTBLDG
Code Description
Existing Building
Chapter
4
Section
405
Topic
fire damage

Question

Is it the intent of section 405 to require the entire building to be brought into compliance with the current code if the building has been damaged by fire such that the cost of repair is more than 50% of the value of the building, similar to old Section 3401.7.2.6 in the 2001 FBC (aka the "50%" rule)?

Answer Published 09/14/2011 at 1:32 PM

No. If there is no alteration (see definition) work being
done - the work is classified as a repair. If there is
alteration work then it falls within the parameters of
405.1 and the work must comply with the requirements in
section 405. However, if the work is classified (by
definition) as a repair, then the work must comply with
chapter 5 only.

Commentary

Keep in mind sections "506.2.2 Substantial structural damage to elements of the lateral-force-resisting system" in which case "the building shall be evaluated by a registered design professional" and section 506.2.2.1and "506.2.3 Substantial structural damage to vertical load-carrying components".