Interpretation #6789

Published July 28, 2011

Original Request

Code Version
2007
Code
BUILDING
Code Description
Building
Chapter
1
Section
419.3.12.1
Topic
Exh.Fan and Alarm System

Question

Is it the intent of of this section to require connection of a 400 cfm exhaust fan, serving only one room, to the fire aalrm system for the purpose of stopping the fan upon activation of the fire alarm system?

Answer Published 07/28/2011 at 10:04 AM

No.

Commentary

None.