Question

Is it the intent of FBC-Building section 706.5 exception #2 and section 707.12 to allow 1 hour rated fire barrier walls enclosing an interior exit stairway to be constructed to the underside of the building’s 1 hour rated roof/ceiling assembly? The stair enclosure walls are masonry and the building roof/ceiling assembly consists of a 5/8 inch Type X drywall ceiling attached to the underside of trusses with attic space and roof deck above.

Answer Published 12/01/2011 at 9:42 AM

No. 707.12 describes the requirement for the top of shafts
that do not extend to the roof.