Interpretation #6759

Published June 02, 2011

Original Request

Code Version
2007
Code
MECHANIC
Code Description
Mechanical
Chapter
3
Section
303.4
Topic
Residential Installations

Question

Is it the intent of FMC 303.4 to apply to residential installations by virtue of the Residential code section M1301.1

Answer Published 06/02/2011 at 11:16 AM

NO. M1401.4 specifically addresses outdoor equipment,
foundations and supports but does not require protection
from vehicular damage. As such, outdoor equipment has been
addressed by the FBCR and therefore one could not go to the
FBC-M to enforce the protection from damage section as
1401.4 has already adressed this installation.

Commentary

Residential code section M1301.1 is there to address installations not mentioned in or specifically covered by the Residential Code.