Interpretation #6735

Published December 01, 2011

Original Request

Code Version
2007
Code
BUILDING
Code Description
Building
Chapter
10
Section
1025.6.2.3
Topic
Means of Egress

Question

Is it the intent of 1025.6.2.3 exception (1) to override the provision of 903.2.1.4 exception where the floor playing surface is a story below the main entrance and exit discharges.

Answer Published 12/01/2011 at 1:38 PM

No. The case stated above does not meet all of the
requirements provided in the exception to 903.2.1.4. The
arena floor is required to be on the same level as
the level of exit discharge. In this case the arena floor
is below the level of exit discharge.

Commentary

None.