Interpretation #6728

Published April 27, 2011

Original Request

Code Version
2007
Code
BUILDING
Code Description
Building
Chapter
9
Section
903.6
Topic
Fire Sprinklers

Question

Is it the intent of Section 903.6 to require the installation of an automated fire sprinkler system in a three-story mixed use building when the second and third stories are occupied by a single dwelling unit with no additional dwelling units located at any level of the structure, and no such sprinkler system is required by any other section of the Code?

Answer Published 04/27/2011 at 9:55 AM

Yes.

Commentary

903.6.1 requires sprinklers in all three-story buildings, and lists exceptions to the requirements. The property described does not meet any of the exceptions. Since it is a mixed use, this building could not be constructed in accordance with the FBC-Residential so the building must be fire sprinkler protected regardless of stories.