Interpretation #6726

Published December 06, 2011

Original Request

Code Version
2007
Code
BUILDING
Code Description
Building
Chapter
16
Section
1618.9
Topic
Structural Loads

Question

Is it the intent of the Florida Building Code to allow stress increase for masonry walls as long as a 25% reduction is not applied for transient loads? This seems to be contradictory to ASCE 7-05 Section 2.4.1 which prohibits stress increase unless it is caused by structural behavior due to rate or duration of loading.

Answer Published 12/06/2011 at 12:54 PM

Yes. This is a Florida Specific Amendment incorporating the
1/3 allowable stress increase provisions of TMS 402/ACI
530/ASCE 5 Section 2.1.2.3 2005 and 2008 Editions.

Commentary

None.