Interpretation #6725

Published December 06, 2011

Original Request

Code Version
2007
Code
BUILDING
Code Description
Building
Chapter
16
Section
1605.3.1.1
Topic
Structural loads

Question

It appears that the 2007 Florida Building Code is not consistent with the requirements of ASCE 7-05. The exception in 1605.3.1.1 allows the increase in allowable stresses in Masonry for load combinations that do not have a 25% reduction for transient loads applied. This is in contradiction to ASCE 7-05 Section 2.4.1 where allowable stress increase is explicitly prohibited unless it is attributed to rate or duration of load.

Answer Published 12/06/2011 at 12:55 PM

This is a Florida Specific Amendment incorporating the
long standing 1/3 allowable stress increase provisions of
TMS 402/ACI 530/ASCE 5 Section 2.1.2.3 (Section number is
relative to 2005 and 2008 Editions.

Commentary

None.