Interpretation #6710

Published April 25, 2011

Original Request

Code Version
2007
Code
BUILDING
Code Description
Building
Chapter
4
Section
423.5.13
Topic
Classroom Spaces

Question

Is it the intent of Florida Building Code that if Classroom(s) have been rearranged by space and/or change of use, those area(s) need to comply with the Florida Building Code for New Construction?

Answer Published 04/25/2011 at 11:09 AM

Yes. If the physical configuration of a space changes, or a
spaces use changes, the reconfigured space or new use is
required to comply with new construction requirements.

Commentary

Because of Section 423.5.14, FBC, Building, public educational facilities are exempted from the Existing Building Code. See Exception to Section 101.2, Existing Building Code.