Interpretation #6690

Published April 15, 2011

Original Request

Code Version
2007
Code
BUILDING
Code Description
Chapter
24
Section
2413.1 And 2411.3.2.5 #7
Topic

Question

Is it the intent of of section 2413.1 to allow
for modification of a window such as removing
the bottom mullion for a kichen pass through if
it is shuttered with approved shutter ?

Answer Published 04/15/2011 at 4:31 PM

No.

Commentary

Wind pressure resistance, forced entry and air infiltration are also to be considered. Product components detailed on a product approval cannot be removed unless indicated in the approval’s limits of use, otherwise the product approval is not valid. Removal of a window’s sill for application as a pass through window requires testing of the unit without the sill. Note that exception #3 in the 2007 FBC section 2411.3.2 is only for the water infiltration test. If impact resistance is provided by use of shutters, then the balance of TAS202 testing requirements apply.