Interpretation #6687

Published April 07, 2011

Download Final PDF

Original Request

Code Version
2007
Code
BUILDING
Code Description
Chapter
6
Section
Table 601
Topic

Question

Is it the intent of the code to require a two
hour fire separation between units in a 9000 sf
retail (Mercantile) condominium building of Type
III construction consisting of less than 1500 sf
per unit or is this considered a tenant
separation with a one hour wall?

Answer Published 04/07/2011 at 4:43 PM

The Florida EXISTING Building Code is the applicable code
for existing buildings.
In regards to the question:
No, it is not the intent of the code to require a two hour
fire rated separation between the units. Occupancy
separation is addressed in 508.3.3. Separation between
tenants would be addressed by 708.1(7) and require a one
hour rating. Additionally, you would still have to provide
for 1hr tenant separation if they are separate tenants.

Commentary

Table 601 is used to determine the minimum fire resistance rating of the building elements based on the type of construction.