Interpretation #6681

Published April 07, 2011

Original Request

Code Version
2007
Code
BUILDING
Code Description
Building
Chapter
17
Section
1714.5.3.2
Topic
Entry Door Testing

Question

Is it the intent of 1714.5.3.2 to allow all entry doors to be rationalized since most homes only have one entryway?

Answer Published 04/07/2011 at 4:40 PM

No. This section applies only to custom door designs. The
"one-of-a-kind" does not relate to the number of doors, but
to whether or not the door is mass produced or a one-time
construction.

Commentary

Exterior doors that are not custom doors are required to be tested by 1714.5.3. The use of a company's test data by others to perform rational analysis circumvents the testing requirement of this section.