Interpretation #6668

Published March 30, 2011

Original Request

Code Version
2007
Code
PLUMBING
Code Description
Plumbing
Chapter
6
Section
607
Topic
master mixing valve

Question

Is the intent of Section 607.1 to require a master mixing valve, conforming to ASSE 1070, on the whole house/building hot water system, in addition to requiring tempering devices on individual fixtures as stated in Section 424?

Answer Published 03/30/2011 at 3:14 PM

No, 607.1 requires hot water, defined as greater than or
equal to 110 degrees for all plumbing fixtures utilized for
bathing, washing, cleansing, laundry, building maintenance
or culinary purposes.

Commentary

Tempered water is permitted in nonresidential occupancies in the exception and the paragraph following the exception refers to nonresidential occupancies.