air space behind electrcial equip.

Question

Is it the intent of Art. 312.2(A) to require a minimum air space behind electrical equipment mounted outside (damp or wet location)?

Answer Published 03/30/2011 at 3:12 PM

312.2 speaks of surface mounted equipment. If you enclose
the equipment with stucco, brick, or other material, that
prevents the 1/4" minimum required clearance, then it is
no longer surface mounted and a violation of its listing and
labeling.

Commentary

Most listed weatherproof metal cabinets are manufactured with a dimple on the back to raise the box off the surface.