Interpretation #6661

Published March 30, 2011

Original Request

Code Version
2007
Code
RESIDENT
Code Description
Residential
Chapter
13
Section
M1301.1
Topic
Mechanical Code

Question

Is it the intent of M1301.1 to apply the requirements of the Florida Building Code- Mechanical to installations that the Residential code is silent on.

Answer Published 03/30/2011 at 3:10 PM

YES, FBCR Part IV, Mechanical, does not address roof mounted
units. FBCR Section M1301.1 Scope. states the following:
"Installations of mechanical appliances, equipment and
systems NOT addressed by this code shall comply with the
applicable provisions of the Florida Building Code,
Mechanical." Therefore, the provisions of FBCR §M1301.1 may
be considered applicable and may be used to invoke the
provisions of the FBC, Mechanical volume.

Commentary

FBC, Section 101.3 ... "the purpose of the code is to establish the minimum requirements to safeguard the public health and safety to life", this includes service personnel and inspectors.