Interpretation #6645

Published March 22, 2011

Download Final PDF

Original Request

Code Version
2007
Code
BUILDING
Code Description
Building
Chapter
7
Section
715.4.7.4
Topic

Question

Is it the intent of the FBC section 715.4.7.4 to allow a fusible link fire shutter to provide a fire rating for an egress door that lacks a fire rating in an open stair of a 3-story structure of type 1B construction?

Answer Published 03/22/2011 at 8:39 AM

A fused steel shutter on an egress door to protect the glass
opening should work but the egress door opening itself
cannot be closed/protected by a shutter [1008.1.2].

Commentary

If the door to be protected is an egress door, a fusible link shutter is not permitted for protection. While 715.4.7.4 addresses doors in pedestrian ways, Egress Doors are specifically governed by Section 1008.