Interpretation #6640

Published March 22, 2011

Original Request

Code Version
2007
Code
BUILDING
Code Description
Building
Chapter
10
Section
1003
Topic
Finish on a balcony

Question

In a high rise condo unit, the balcony has a door which locks from the inside. To exit the unit one must walk across a smooth marble floor to either of two exit doors, which are kept locked from the inside. One opens to an elevator lobby which has a smooth tile floor. This is normally used for entrance and exit. The other door is an emergency exit to a catwalk. The elevator has a smooth marble floor. It exits to a lobby with a smooth marble floor, or to the garage which has a concrete floor. Chapter 10, Section 1002 Defines Means of Egress "A continuous and unobstructed path...from any occupied portion... "Section 1003.4 Refers to floor surface.1003.6 refers to Means of Egress continuity, specifying no obstructions. Question. Can the balcony have a smooth floor? question

Answer Published 03/22/2011 at 9:13 AM

IF the floors in question are part of the means of egress,
then section 1003.4 would require them to be "slip-resistant
under foreseeable conditions" and "uniformly slip resistant
along the natural path of travel."

Commentary

None.