704.1
Topic
termite protection

Question

Is it the intent of SECTION R704 INSPECTION FOR TERMITES to not allow a 4-inch (102 mm) inspection space above patio and garage slabs and entry areas?

Answer Published 06/11/2012 at 3:19 PM

Section 704.1 requires a 6" clearance between the exterior
finish and grade. Exception 3 may apply in an instance
where the garage is enclosed. This requires a 4" clearance
between the concrete drive (or now a patio) and the new
exterior siding.

Commentary

Exception 3 is not specific to garage only, it also refers to patios and entry areas - so it could be to a habitable or usable space that is adjacent to concrete.