Interpretation #6635

Published September 20, 2010

Original Request

Code Version
2007
Code
BUILDING
Code Description
Building
Chapter
24
Section
2411 and 2414
Topic
design vs NOA

Question

Is it the intent of the Building Code to allow professional structural engineers to design the anchorage of glazing systems that differ from the products NOA do to substrate, or geometry, or pressure requirements?

Answer Published 09/20/2010 at 11:21 AM

Yes. Diverging from a product approval, be it local
approval, an authorized testing lab or NOA sheet, or
Florida approval number places the responsibility on the
design professional. Please see the commentary for
additional information.

Commentary

A properly registered design professional (engineer, for example) may submit drawings as a "design" in accordance with the product approval rule for local approval to the local official as the system was intended (Step 1). A design professional may also take testing data and provide it with appropriate documentation as an alternate method to the local official for approval (Step 2). The last step of the product approval process, Step 3, is to use a product approval number, or NOA. The building code did not intend to take away the ability of the local official to approve appropriate designs and this process is in comformance with the building code.