Interpretation #6633

Published September 20, 2010

Original Request

Code Version
2007
Code
BUILDING
Code Description
Chapter
16
Section
1626.4
Topic

Question

Is it the intent of 1626.4 "All connectors shall
be specified by the building designer of record
for all loads except impact" To prohibit a
designated engineer for designing the connection
and does loads except impact loads refer you to
the load combination in section 1605?

Answer Published 09/20/2010 at 11:21 AM

Diverging from the product approval, be it an NOA, Florida
Approval, or local approval negates the approval. The
engineer could submit the changes as an alternate method to
the local official for approval, however, the installation
would not be in accordance with the NOA.

Commentary

None.