Is it the intent of 1626.4 "All connectors shall
be specified by the building designer of record
for all loads except impact" To prohibit a
designated engineer for designing the connection
and does loads except impact loads refer you to
the load combination in section 1605?
Interpretation #6633
Published September 20, 2010
Original Request
- Code Version
- 2007
- Code
- BUILDING
- Code Description
- Chapter
- 16
- Section
- 1626.4
- Topic
Question
Answer Published 09/20/2010 at 11:21 AM
Diverging from the product approval, be it an NOA, Florida
Approval, or local approval negates the approval. The
engineer could submit the changes as an alternate method to
the local official for approval, however, the installation
would not be in accordance with the NOA.
Approval, or local approval negates the approval. The
engineer could submit the changes as an alternate method to
the local official for approval, however, the installation
would not be in accordance with the NOA.