Interpretation #6624

Published September 20, 2010

Original Request

Code Version
2007
Code
MECHANIC
Code Description
Mechanical
Chapter
6
Section
603.6
Topic
attachment of diffusers

Question

Is it the intent of the mechanical or building code to allow the air diffusers to be sealed and taped to the accoustical ceiling grid?

Answer Published 09/20/2010 at 11:17 AM

Yes, if the ceiling grid constitutes part of the
"Building envelope- semiexterior" (see Chapter 13 definitions).
If the ceiling grid is not considered part of the "building
envelope-semiexterior", then the requirements of 603.6.2
would not allow it.

Commentary

Per 603.6.1 all materials used must be "approved" closure systems.