Is it the intent of the 2007 FPC Section 1003.3.2
to require food waste grinders to pass thru a
solids interceptor prior to entering a 1250
gallon grease interceptor? Or is this section of
code only pertaining to food watse grinders that
connect to smaller manufactured grease
interceptors that conform to ASME A112.14.3 and
PDI G101.
Interpretation #6607
Published August 29, 2010
Original Request
- Code Version
- 2007
- Code
- PLUMBING
- Code Description
- Chapter
- 10
- Section
- 1003.3.2
- Topic
Question
Answer Published 08/29/2010 at 12:13 PM
Yes, if for some reason the owner or designer want the
discharge of the food waste grinder to be connected to the
grease interceptor. If the designer chooses to discharge
through a grease interceptor, it must first pass through a
solids interceptor so as prevent food and debris from
impeding the function of the interceptor. The code permits
but does not require that food waste grinders discharge
through a grease interceptor.
discharge of the food waste grinder to be connected to the
grease interceptor. If the designer chooses to discharge
through a grease interceptor, it must first pass through a
solids interceptor so as prevent food and debris from
impeding the function of the interceptor. The code permits
but does not require that food waste grinders discharge
through a grease interceptor.
Commentary
This requirement is intended to apply to all grease
interceptors, large and small, inside or outside, connected
to private or public sewer systems. Section 1003.3.1 does
not list "food waste grinder" among the fixtures and
equipment that are required to be connected to grease
interceptors. Traditionally, if only cold water is
connected to the food waste grinder, the solids are ground
up and mixed with cold water so as to prevent the
emulsification of grease or oil in the food. Ground solid
waste is then able to enter the sewer system unimpeded by
grease interceptors or solids interceptors. And it does so,
without depositing emusified grease to coagulate and clog
the pipes. In other words, neither a grease interceptor nor
a solids interceptor is required by the Code for a food
waste grinder. The local sewer treatment authority may have
different applicable regulations.