Interpretation #6604

Published August 29, 2010

Download Final PDF

Original Request

Code Version
2007
Code
MECHANIC
Code Description
Chapter
4
Section
403.3
Topic

Question

Is it the intent of Table 403.3 to upgrade the
ventilation requirements of a business
classification 'office' space to a business
classification 'college classroom' space under
2007 FBC Existing Building/Mechanical?

Answer Published 08/29/2010 at 12:11 PM

In this case, the occupancy classification remains a
Business, the use is changing from an office to a
classroom. Table 403.3 stipulates a far greater occupany
load per 1000 sq. ft. for classrooms than for offices (50
people per 1000 vs. 7 people) and as such would require
additional ventilation air be provided to the space.

Commentary

403.3 provides the ventilation guidelines for different occupancy classifications and uses of spaces within buildings. Table 403.3 is enforceable in existing structures when compliance with the following sections is required: 901.2.1 Repair and alteration with no change of occupancy classification. Any repair or alteration work undertaken in connection with a change of occupancy that does not involve a change of occupancy classification shall conform to the applicable requirements for the work as classified in Chapter 4 and to the requirements of Sections 902 through 911. 909.1 Mechanical requirements. Where the occupancy of an existing building or part of an existing building is changed such that the new occupancy is subject to different kitchen exhaust requirements or to increased mechanical ventilation requirements in accordance with the Florida Building Code, Mechanical. The intent of the respective Florida Building Code, Mechanical provisions shall be complied with for the new occupancy.