Is it the intent of Table 403.3 to upgrade the
ventilation requirements of a business
classification 'office' space to a business
classification 'college classroom' space under
2007 FBC Existing Building/Mechanical?
Interpretation #6604
Published August 29, 2010
Original Request
- Code Version
- 2007
- Code
- MECHANIC
- Code Description
- Chapter
- 4
- Section
- 403.3
- Topic
Question
Answer Published 08/29/2010 at 12:11 PM
In this case, the occupancy classification remains a
Business, the use is changing from an office to a
classroom. Table 403.3 stipulates a far greater occupany
load per 1000 sq. ft. for classrooms than for offices (50
people per 1000 vs. 7 people) and as such would require
additional ventilation air be provided to the space.
Business, the use is changing from an office to a
classroom. Table 403.3 stipulates a far greater occupany
load per 1000 sq. ft. for classrooms than for offices (50
people per 1000 vs. 7 people) and as such would require
additional ventilation air be provided to the space.
Commentary
403.3 provides the ventilation guidelines for different
occupancy classifications and uses of spaces within
buildings. Table 403.3 is enforceable in existing
structures when compliance with the following sections is
required:
901.2.1 Repair and alteration with no change of occupancy
classification. Any repair or alteration work undertaken in
connection with a change of occupancy that does not involve
a change of occupancy classification shall conform to the
applicable requirements for the work as classified in
Chapter 4 and to the requirements of Sections 902 through
911. 909.1 Mechanical requirements.
Where the occupancy of an existing building or part of an
existing building is changed such that the new occupancy is
subject to different kitchen exhaust requirements or to
increased mechanical ventilation requirements in accordance
with the Florida Building Code, Mechanical.
The intent of the respective Florida Building Code,
Mechanical provisions shall be complied with for the new
occupancy.