Interpretation #6599

Published August 19, 2010

Original Request

Code Version
2004
Code
BUILDING
Code Description
Building
Chapter
22
Section
2220.3
Topic
Steel Protection

Question

Is it the intent of Florida Building Code - Building Section 2220.3 to consider UL listed fireproofing material as an "other approved material" whereby the steel would not be required to have the shop and field coatings applied?

Answer Published 08/19/2010 at 6:26 PM

No.

Commentary

The "coatings" the code is referring to is "a corrosion- resistive metallic coating" not a fireproofing coating. In addition, "approved" as defined by the code means "Acceptable to the code official or authority having jurisdiction."