Interpretation #6595

Published August 19, 2010

Original Request

Code Version
2007
Code
BUILDING
Code Description
Building
Chapter
10
Section
1006.2.3
Topic
Egress Lighting

Question

Is it the intent of Florida Building Code - Building Section 1006.2.3 to require means of egress lighting to be equipped with battery back-up even when the means of egress lighting is powered by two completely separate and circuited power sources, one being utility supplied power and the other an emergency generator?

Answer Published 08/19/2010 at 6:23 PM

It depends. Please see the attached commentary.

Commentary

The question does not state if this is a legally required system or not. It appears to state an emergency "system" is installed with completely separate wiring systems with no connection to each other and yet does not state if an automatic transfer switch is installed or if the generator will pick up any loads within the required 10 seconds. Other issues may also need to be addressed, including occupancy and load. An emergency power system is generally designed and supplied by both normal and generator power. In some cases, it is relay controlled to transfer power from a normal source to an emergency source using a transfer switch. If normal power is lost, a generator will feed the emergency system through the automatic transfer switch. The code does not generally intend to require three different sources of power. Additionally, a DEC statement that was issued by the State Fire Marshal a few years ago specifically allows this condition in a specific case. Further, if half the lights are on "normal" power and half are on "emergency," no one manual act could leave the path of egress in darkness, because the distributions are separate all the way to the source of supply. If the source of supply fails, the generator kicks in. While the question is based in the building volume, careful reading of the documentation indicates the NEC allows an alternate (second) power source from the utility if it is deemed reliable. If only the standard utility source is used, a battery backup system would be required. If a generator capable of picking up the load within 10 seconds and tested in accordance with the governing documents is used, the code allows that as it is not depending on the power company. The building code commentary provides reference to the utility and NEC requirements and the commentary does not disallow the generator.