Interpretation #6593

Published August 19, 2010

Original Request

Code Version
2007
Code
BUILDING
Code Description
Building
Chapter
9
Section
907.3.1
Topic
Fire Alarms

Question

Is it the intent of Florida Building Code - Building Section 907.3.1 to require manual fire alarm boxes to be located inside a space, such as a classroom in a public educational facility, not more than 5 feet from the classroom's only door which exits directly to the exterior or can the pull station be located outside the classroom’s single exit door?

Answer Published 08/19/2010 at 6:06 PM

It depends. It is the intent of the code to require the
pull stations to be on the inside of the exit door. Simply
leading to the outside may not necessarily make a door an
exit, as opposed to exit access or means of egress. The
requestor does not specify whether the door from the
classroom leads into a restricted pathway which depending
on arrangement could still be part of the exit access.
Please see the attached commentary.

Commentary

DOE enforces this requirement as follows: Pull stations are required by NFPA 72- 5.12.6 (02 Edition) and 5.13.6 (07 Edition) to be located within 5 feet of the “exit doorway” or “exit access.” The pull station shall not be obstructed by the swing of the door or any object/material. Therefore, if a first floor classroom exits directly to the exterior, it shall have a pull station at the door. However, if the classroom exits into a designed path that does not allow random exiting but requires the evacuees to follow an exterior hall/corridor, one side is the building and the other has a physical barrier, then the “exit doorway” or “exit access” is at the point where the physical barrier ends. The placement of the pull station at each barrier end point meets the NFPA 72 requirements. Any other first floor classroom that does not open onto the designed exit path is required to have a pull station inside the room. The two hundred (200) foot rule {NFPA 72-5.12.8 (02 Edition) and 5.13.8 (07 Edition} for placing pull stations shall also apply. For multi-story buildings, a pull station is required at the head of all stairways exiting the floor and also at 200 foot intervals on the floor along the egress path.