Interpretation #6590

Published July 08, 2010

Original Request

Code Version
2007
Code
FUELGAS
Code Description
Fuel Gas
Chapter
4
Section
403.9
Topic
Piping Materials

Question

Is it the intent of Florida Building Code - Fuel Gas Section 403.9 and the referenced standard, ASME B1.20.1 to allow the use of pipe nipples with "running threads" for gas piping installations?

Answer Published 07/08/2010 at 9:29 AM

No. Florida Building Code - Fuel Gas Section 403.9 states
that "Metallic pipe and fitting threads shall be TAPER pipe
threads and shall comply with ASME B1.20.1". Continuously
threaded pipe nipples, or "running" thread nipples do not
produce a tapered thread, are not compatible with pipe
fittings and as such, do not provide a gas tight seal.

Commentary

None.