Interpretation #6577

Published July 08, 2010

Original Request

Code Version
2007
Code
ELECTRIC
Code Description
Electrical
Chapter
4
Section
406.11
Topic
Receptacles

Question

Is it the intent of Section 406.11 of the 2008 NEC to require receptacles installed on a new arc fault circuit to be tamper resistant when converting a lanai into a bedroom in a single family dwelling?

Answer Published 07/08/2010 at 5:44 PM

Yes. Per Florida Building Code - Existing Building Section
404.1, the installation of a new electrical circuit would be
classified as a Level 2 Alteration. FBC - Existing Building
Section 708.1 requires all newly installed electrical
equipment and wiring relating to work done in any work area
to comply with the materials and methods requirements of FBC
- Building Ch. 27. Article 406.11 of the 2008 NEC requires
that in all areas specified in 210.52, all 125-volt, 15 and
20 ampere receptacles shall be listed tamper-resistant
receptacles.

Commentary

Per 210.52(A) General Provisions. In every kitchen, family room, dining room, living room, parlor, library, den, sunroom, bedroom, recreation room, or similar room or area of dwelling units, receptacle outlets shall be installed in accordance with the general provisions specified in 210.52 (A)(1) through (A)(3).