Question

Is it the intent of Florida Building Code - Building Section 715 to require smoke and draft control doors in fire rated corridors when the doors in the fire rated corridor are fire resistant rated assemblies?

Answer Published 07/02/2010 at 1:35 PM

Yes. Florida Building Code - Building Section 715.3.3
states, in part that "...fire door assemblies shall also
meet the requirements for smoke and draft control door
assembly tested in accordance with with UL 1784...".