Interpretation #6572

Published July 02, 2010

Original Request

Code Version
2004
Code
RESIDENT
Code Description
Residential
Chapter
41
Section
R4101.6.1
Topic
Pool & Spa Design

Question

Is it the intent of Florida Building Code - Residential Section R4101.6.1 and the reference to ANSI/NSPI-3 Residential Spa Standard to cover ALL seats/sitting bench at a maximum water depth of 28" and not just only "Muti-level seating"? In a residential spa, what is the maximum water depth to the single depth seat/sitting bench?

Answer Published 07/02/2010 at 1:35 PM

Yes. Although the provision is found in Florida Building
Code - Residential Section R4101.6.1, Multi-Level Seating,
the provision does not apply solely to multi-level seating,
but establishes the maximum depth of any seat.

Commentary

From NSI-NSPI- 3-1999: "5.3 Multi-Level Seating: Multi-level seating may be provided, but the maximum water depth of ANY seat or sitting bench shall be twenty-eight inches (28") [71.12 cm] measured from the waterline."